Chapter 20, Problem 1SQ

Using the schematic diagram in Figure 20–23, determine the number of control wires needed to control the three-phase motor. Use the terminal and wire identification shown in the schematic as well as proper power circuit identification.

Chapter 20, Problem 1SQ, Using the schematic diagram in Figure 2023, determine the number of control wires needed to control

FIG. 20–23

Expert Solution & Answer
Check Mark
To determine

Calculate the number of control wires required to control the three-phase motor in Figure 20–23.

Explanation of Solution

The 3 wires are connected to the externally operated disconnect switch, and the switch is connected to pull box through 3 wires. Four wires are used to connect stations 1 and 2. Four wires and three wires are used to connect station 2 and station 3 to pull box, respectively. The pull box is connected to motor starter using 6 wires, and finally, starter is connected to a three-phase motor using 3 wires. Redraw the given figure with the representation of the required control wires as shown in Figure 1.

Electric Motor Control, Chapter 20, Problem 1SQ

Conclusion:

Thus, the number of control wires required to control the three-phase motor in Figure 20-23 is calculated.

Want to see more full solutions like this?

Subscribe now to access step-by-step solutions to millions of textbook problems written by subject matter experts!
Students have asked these similar questions
Why are stranded copper wire is used instead of solid copper wirename the four types of battery capacity rating What type of engine conversion occurs when the battery is discharging? List the seven components of the starting system List the four most common start a customer complaints What is the name of the stationary coil that produces current in the AC generator? what is the name of the company that creates the rotating mechanical field of the AC generator?
Draw the block diagram and clearly explain the operation of diesel power station.
5. A 15-HP motor operates at full-load from a 600 V, 3-phase, 60 Hz, delta connected source. The motor is 75% efficient and its power factor is 0.82 lagging. a. Calculate the line and phase currents b. Draw the circuit identifying one line voltage and line current. Also identify one phase voltage and one phase current on the source. C. What is the power generated by one phase of the delta connected source?

Chapter 20 Solutions

Electric Motor Control

Knowledge Booster
Background pattern image
Electrical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
Electric Motor Control
Electrical Engineering
ISBN:9781133702818
Author:Herman
Publisher:CENGAGE L
Types of Protective Relays and Design Requirements, Part 1a.; Author: GeneralPAC: Power System Tutorials;https://www.youtube.com/watch?v=JYil4T5VSDM;License: Standard Youtube License