The three-phase power and line-line ratings of the electric power system shown in Figure 30 are given below. Vg OBH G T2 2 Vm Line M FIGURE 30 One-line diagram for Problem 3.15 G₁: 60 MVA 20 kV X = 9% T₁: 50 MVA 20/200 kV X = 10% T2: 50 MVA 200/20 kV X = 10% M: 43.2 MVA 18 kV X = 8% Line: 200 kV Z 120+j200 $2 (a) Draw an impedance diagram showing all impedances in per unit on a 100-MVA base. Choose 20 kV as the voltage base for generator. (b) The motor is drawing 45 MVA, 0.80 power factor lagging at a line-to-line ter- minal voltage of 18 kV. Determine the terminal voltage and the internal emf of the generator in per unit and in kV.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.33P: Consider the three single-phase two-winding transformers shown in Figure 3.37. The high-voltage...
icon
Related questions
Question
The three-phase power and line-line ratings of the electric power system
shown in Figure 30 are given below.
Vg
OBH
G
T2
2
Vm
Line
M
FIGURE 30
One-line diagram for Problem 3.15
G₁:
60 MVA
20 kV
X = 9%
T₁:
50 MVA
20/200 kV
X = 10%
T2:
50 MVA
200/20 kV
X = 10%
M:
43.2 MVA
18 kV
X = 8%
Line:
200 kV
Z
120+j200 $2
(a) Draw an impedance diagram showing all impedances in per unit on a 100-MVA
base. Choose 20 kV as the voltage base for generator.
(b) The motor is drawing 45 MVA, 0.80 power factor lagging at a line-to-line ter-
minal voltage of 18 kV. Determine the terminal voltage and the internal emf of the
generator in per unit and in kV.
Transcribed Image Text:The three-phase power and line-line ratings of the electric power system shown in Figure 30 are given below. Vg OBH G T2 2 Vm Line M FIGURE 30 One-line diagram for Problem 3.15 G₁: 60 MVA 20 kV X = 9% T₁: 50 MVA 20/200 kV X = 10% T2: 50 MVA 200/20 kV X = 10% M: 43.2 MVA 18 kV X = 8% Line: 200 kV Z 120+j200 $2 (a) Draw an impedance diagram showing all impedances in per unit on a 100-MVA base. Choose 20 kV as the voltage base for generator. (b) The motor is drawing 45 MVA, 0.80 power factor lagging at a line-to-line ter- minal voltage of 18 kV. Determine the terminal voltage and the internal emf of the generator in per unit and in kV.
Expert Solution
steps

Step by step

Solved in 2 steps with 4 images

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning