Plant L: 100kVA, 0.68pf lagging Plant K: 60kVA, 0.65pf lagging It is desired to correct the power factor of the two plants by connecting a synchronous motor. When the synchronous motor is connected, the overall power factor is corrected to 0.95 lagging. At what power factor is the synchronous motor operates if it is operating at 80kW

Electric Motor Control
10th Edition
ISBN:9781133702818
Author:Herman
Publisher:Herman
Chapter39: Synchronous Motor Operation
Section: Chapter Questions
Problem 11SQ: Varying the DC voltage to the rotor field changes the a. motor speed. b. power factor. c. phase...
icon
Related questions
Question

Plant L: 100kVA, 0.68pf lagging
Plant K: 60kVA, 0.65pf lagging
It is desired to correct the power factor of the two plants by connecting a synchronous motor. When the synchronous motor is connected, the overall power factor is corrected to 0.95 lagging. At what power factor is the synchronous motor operates if it is operating at 80kW

Expert Solution
steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Knowledge Booster
Economic load dispatch
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Electric Motor Control
Electric Motor Control
Electrical Engineering
ISBN:
9781133702818
Author:
Herman
Publisher:
CENGAGE L
Electricity for Refrigeration, Heating, and Air C…
Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning