Explain the reasons for applying system grounding in electric power systems.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter9: Unsymmetrical Faults
Section: Chapter Questions
Problem 9.13P: Consider the oneline diagram of a simple power system shown in Figure 9.20. System data in per-unit...
icon
Related questions
Question
Problem 6
a- Explain the reasons for applying system grounding in electric power systems.
Consider the industrial plant distribution bus which is supplied by a utility source with per-unit
sequence reactances as shown in Figure (4-a). Assume that all reactances are given on a 5,000-kVA
base, and that the plant's bus voltage is 4,160-V.
b- Determine the fault current for a single line to ground fault on phase A of the bus.
Assume now that an ungrounded 5,000 kVA generator is added at the distribution bus as shown in
Figure (4-b).
c- Determine the fault current for a single line to ground fault on phase A of the bus.
Assume now that the utility transformer is grounded through a 8 2 grounding resistor as shown in
Figure (4-c.)
d- Determine the value of the grounding resistor in per unit.
e- Determine the fault current for a double line to ground fault on phases B and C of the bus.
Transcribed Image Text:Problem 6 a- Explain the reasons for applying system grounding in electric power systems. Consider the industrial plant distribution bus which is supplied by a utility source with per-unit sequence reactances as shown in Figure (4-a). Assume that all reactances are given on a 5,000-kVA base, and that the plant's bus voltage is 4,160-V. b- Determine the fault current for a single line to ground fault on phase A of the bus. Assume now that an ungrounded 5,000 kVA generator is added at the distribution bus as shown in Figure (4-b). c- Determine the fault current for a single line to ground fault on phase A of the bus. Assume now that the utility transformer is grounded through a 8 2 grounding resistor as shown in Figure (4-c.) d- Determine the value of the grounding resistor in per unit. e- Determine the fault current for a double line to ground fault on phases B and C of the bus.
Utility
5,000
KVA
Utility
Gen
X=0.15
X= 0.06
X- 0.15
X = 0.15
X = 0.06
X = 0.15
X- 0.1
Xo = 0.04
X= 0.1
Plant Distribution Bus
Plant Distribution Bus
(a)
(b)
5,000
KVA
Utility
uly
Gen
X= 0.06
x,-0.15
X = 0.06
X = 0.15
Xo = 0.04
X- 0.1
%3D
Plant Diatribution Bus
(c)
Figure (4) Single-line diagrams for Problem 6
Transcribed Image Text:Utility 5,000 KVA Utility Gen X=0.15 X= 0.06 X- 0.15 X = 0.15 X = 0.06 X = 0.15 X- 0.1 Xo = 0.04 X= 0.1 Plant Distribution Bus Plant Distribution Bus (a) (b) 5,000 KVA Utility uly Gen X= 0.06 x,-0.15 X = 0.06 X = 0.15 Xo = 0.04 X- 0.1 %3D Plant Diatribution Bus (c) Figure (4) Single-line diagrams for Problem 6
Expert Solution
steps

Step by step

Solved in 5 steps with 5 images

Blurred answer
Knowledge Booster
HVDC
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Electric Motor Control
Electric Motor Control
Electrical Engineering
ISBN:
9781133702818
Author:
Herman
Publisher:
CENGAGE L