A 90-MVA 69.3-kV, three-phase synchronous generator has a synchronous reactance of 10 Ohms/phase and negligible armature resistance. The generator is delivering power to the bus bar at the rated voltage with its field current adjusted for a generated emf (excitation voltage) of 50 kV per phase and a power angle & = 7.1 degree. Thus, the delivered power is the generator armature current is and the power factor is

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
power before losing synchronism (stability limit).
Thus, the maximum generated power is Pmax =
+ and the armature current is la =
A 90-MVA 69.3-kV, three-phase synchronous generator has a synchronous reactance of 10 Ohms/phase and negligible
armature resistance. The generator is delivering power to the bus bar at the rated voltage with its field current adjusted
for a generated emf (excitation voltage) of 50 kV per phase and a power angle & = 7.1 degree.
Thus, the delivered power is
the generator armature current is
and the
power factor is
The three phase power and line-line ratings of the below electric power system is given below:
Vg
Vm
M
G: 50 MVA
20 KV
X= 4%
T: 50 MVA
20/40 KV
X= 4%
43.2 MVA
36 KV
X= 40%
1:49 A
EN
4040
Transcribed Image Text:power before losing synchronism (stability limit). Thus, the maximum generated power is Pmax = + and the armature current is la = A 90-MVA 69.3-kV, three-phase synchronous generator has a synchronous reactance of 10 Ohms/phase and negligible armature resistance. The generator is delivering power to the bus bar at the rated voltage with its field current adjusted for a generated emf (excitation voltage) of 50 kV per phase and a power angle & = 7.1 degree. Thus, the delivered power is the generator armature current is and the power factor is The three phase power and line-line ratings of the below electric power system is given below: Vg Vm M G: 50 MVA 20 KV X= 4% T: 50 MVA 20/40 KV X= 4% 43.2 MVA 36 KV X= 40% 1:49 A EN 4040
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 3 steps with 2 images

Blurred answer
Knowledge Booster
Stability Analysis in Power System
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,